I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?
In the system definition, group-type slave stations in any I/O configuration are registered as 'DeviceNet capsule.' In addition, the numbers of input and out...
Show Detail
-
What happens when I set the key switch of the operating CPU to STOP while using the redundancy function of the SPH300? Is the operation switched t...
This only stops the operating CPU and the operation is not switched to the standby CPU.
Show Detail
- No:1588
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Which is the signal that indicates pulse output completion on the positioning control module (Type_ NP1F-MP2)?
Pulse output completion is indicated by the 'Command pulse zero' signal.
Normally, it is '1' to indicate the status of completion. When the number of pulses...
Show Detail
- No:1548
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Is it possible to have redundant (duplicate) Ethernet communication via the Ethernet interface module (Type_ NP1L-ET1/ET2) in a redundant system of...
The redundant function of the SPH Series provides redundancy only for the CPU and it cannot make the Ethernet redundant.
Show Detail
-
When I try to register a remote I/O master module using the I/O extension function in a multi-CPU configuration in the system definition, an error ...
No, you cannot use the I/O extension function in a multi-CPU configuration.
Register a remote I/O master module in the normal mode or extension mode in a...
Show Detail
- No:1651
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
The feedback pulses of the pulse train duplex positioning control module (Type_ NP1F-MP2) have A and B phases only and do not have Z-phase pulses. ...
The module counts feedback pulses even without Z-phase pulse signals.
Note that when Z-phase pulse signals are not provided, origin return operation is dis...
Show Detail
- No:1549
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
The SPH300, SPH2000, and SPH3000 series CPU modules can mount a compact flash card (CF card) or an SD card. Is it necessary for normal operation?
No, it is not necessary for normal operation.
The main purposes of mounting a CF card or an SD card on a CPU module are as follows.
- You can write a progr...
Show Detail
- No:1474
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/09 13:31
- Category:
Main unit
-
Is it possible to use an encoder of the complementary output type for the high-speed counter module (Type_ NP1F-HC2)?
No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ...
Show Detail
- No:1320
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, ho...
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro...
Show Detail
-
During loader command communication of Ethernet, a port is closed after it has not been accessed from a personal computer for a certain period of t...
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if...
Show Detail