Only when the MICREX-F CPU is F55/F70/F70S/F80H/F120H/F120S to F150S, you can connect a MICREX-SX series T-link interface module although the order of the bi... Show Detail
In Standard loader, to access the input memory from MONITOUCH, cancel the I/O group setting of the input specified as 'no equipment.' If the input specified... Show Detail
This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
To use a CF card as user ROM of the SPH Series, you need to format the CF card and initialize it (generate folders and files in the user ROM). The format sh... Show Detail
Doesn't the connector type I/O module of the SPH Series include a connector as an accessory?
The SPH Series does not include an I/O connector. A soldering type connector is available as an option sold separately (NP8V-CN). Show Detail
No, it does not support the DPV1 function. It supports the DPV0 (I/O communication) function. Show Detail
Selecting the DCE mode for the communication parameter_ DCE designation keeps DSR always on. Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail