For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
Please describe the product SX communication middleware (Type_ NP4N-MDLW).
It is a local/remote data server (OPC server) compatible with Data Access (DA2.0) proposed by OPC (OLE for Process Control) extending OLE/COM for process con... Show Detail
Set the port No. as described below. (1) For NP1L-RS2_ Set '0.' (2) For NP1L-RS4_ Set '1.' See the figure below for the setting for each type of genera... Show Detail
Can I perform broadcast communication between CPU modules without using FL-net or P/PE-link module?
The general-purpose communication function of Ethernet allows simplified broadcast communication. By using a CPU with built-in Ethernet, you can build a bro... Show Detail
What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module. Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail