The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
What is the transfer data size range for the READ_WORD/WRITE_WORD FB?
The range in terms of description is up to 4096 words respectively. Note, however, that actual message transfer on the SX bus takes place after division into... Show Detail
The SPH3000 series has 'high-speed program (high-speed PG) memory' area in the program memory. When you store a POU in this area, the POU execution speed be... Show Detail
Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
Can I use a router for FL-net?
You cannot use a router because FL-net does not support the use of subnet. *Related document: For the notes on using FL-net, refer to 'Appendix 2-8 Differen... Show Detail
Common memory 1 and common memory 2 are handled together in terms of timing. However, to maintain the uniqueness of data including those in common memory 1 a... Show Detail
It depends on your CPU model and how often you conduct regular inspection. The backup time after a battery error is detected is as follows. NP1PS-32/32R:... Show Detail
21-30 of Total 235