You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
What is necessary for MODBUS_TCP communication between SPH and an external device?
The following are necessary. 1) Hardware Ethernet interface module (NP1L-ET1) or CPU module with built-in Ethernet (SPH2000/3000 series CPU types w... Show Detail
Only when the MICREX-F CPU is F55/F70/F70S/F80H/F120H/F120S to F150S, you can connect a MICREX-SX series T-link interface module although the order of the bi... Show Detail
NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
What is the difference between the LG and FG terminals of the power supply module (Type_ NP1S-22)?
The LG terminal is a line filter ground terminal in the power supply module. It is intended for guiding any external noise produced in the power supply or sw... Show Detail