Does the PROFIBUS-DP master/slave module (Type_ NP1L-PD1/PS1) support the DPV1 (message communication) function?
No, it does not support the DPV1 function.
It supports the DPV0 (I/O communication) function.
Show Detail
-
What will happen to the station number assigned to each slot of a base board with a station number setting switch (Type_ NP1BS-**S, NP1BP-13S, NP1B...
The SX bus station number for the slot on which the CPU module is mounted is recognized as unused.
Show Detail
- No:1382
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Is there a battery available with a longer backup time than the backup battery for SPH (Type_ NP8P-BT)?
There is a high-capacity battery for SPH300 (Type_ NP8P-BTS). Its battery capacity (approximately 2700 mA) is about 2.7 times that of the backup battery supp...
Show Detail
- No:1360
- Displayed Date:2023/04/25 19:00
- Category:
Accessory
-
How can I write to the user ROM card of a standard CPU?
Turn off the write-protect switch of the user ROM card, mount it on the CPU module and transfer a program to write it to the user ROM card.
Show Detail
- No:1344
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
On the high-speed output module (Type_ NP1Y32T09P1-A), the ONL/ERR lamps are illuminated. Why does this happen?
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A).
Show Detail
- No:1342
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
What is the difference in the open-collector pulse input between the high-speed counter (Type_ NP1F-HC2) and the multi-channel counter (Type_ NP1F-...
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req...
Show Detail
- No:1341
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When the pulse catch function of the high-speed input module (Type_ NP1X3206-A) is used, can all points be used? Is any difference made to the puls...
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8.
With ports 9 to 32, pu...
Show Detail
- No:1321
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:17
- Category:
Function
-
Does the built-in ALM contact of the power supply module of SPH maintain its status (contact closed) even if the power supply recovers to normal af...
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open).
Show Detail
- No:1289
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Do the blue and white cables for the ALM output of the power supply module (Type_ NP1S-22) have polarity?
No, they do not have polarity because they use relay contacts.
Show Detail
- No:1585
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
How long is the refresh cycle of the pulse count value data of the high-speed counter module (Type_ NP1F-HC2)?
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle...
Show Detail
- No:1547
- Displayed Date:2023/04/25 19:00
- Category:
Function