For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
_F_WRITE_CSV_DINT' may be influenced by the file search time depending on the number of files in the CF. The time it takes for 100 (200-word) DINT data to b... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
What is necessary for MODBUS_TCP communication between SPH and an external device?
The following are necessary. 1) Hardware Ethernet interface module (NP1L-ET1) or CPU module with built-in Ethernet (SPH2000/3000 series CPU types w... Show Detail
NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro... Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
Yes, it is possible. Of the parameter setting items of initialization, changes made to specific parameter items (such as frame detection, code conversion and... Show Detail
You can connect an SX series CPU to D300win via USB, Ethernet or a dedicated loader cable, depending on the model. Configure the communication settings acco... Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail