Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A). Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't. Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica... Show Detail
In exponentiation operation, when a negative value is used for the base, the result is 0. Show Detail
For what application is the base board with station number setting switch used?
It is used as a base specified for 'system fail-soft start-up' operation, which is set when there is any base with some modules on which power is not turned ... Show Detail
Yes, it is the same. Show Detail
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail
While 'DTR_ terminal ready' can be used with RS-232C, this control line is not present for RS-485. If no response is received while data are exchanged, re... Show Detail