The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
I want to equalize filter instructions in a redundant system.
Filter instructions are system FBs. System FBs that can be equalized are limited to_ The last value of the edge detection FB, present counter value of the co... Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
I don't have the SX bus loop-back plug (Type_ NP8B-BP). Can I use the SX bus cable instead?
You can use it provided that the system is a single-unit system (configured with one base only). Connect the connectors at both ends of the cable to IN and ... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca... Show Detail
The simulation function of the StandardV3 does not support the index register. Check the program operation using a hardware PLC. Show Detail
The high-speed output module (Type_ NP1Y32T09P1-A)/high-speed input module (Type_ NP1X3206-A) cannot be mounted on the T-link expansion (RT1). Show Detail
I want MICREX-SX SPH models designed to resist sulfurized gas.
You can order sulfurized gas-resistant models by adding /Z4 at the end of product type code of the MICREX-SX SPH. Or, contact your Fuji Electric sales repres... Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
171-180 of Total 235