The memory usage is displayed in 'GM (global memory)' by the 'Device' function that is used to edit tags or check the memory usage. However, the memory cap... Show Detail
You can use it as a standard base board by setting its station No. to '00.' In this case, you also need to set the system definition of the loader designed f... Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
Both the pulse output and control output are open collector outputs. They should be used within the following ranges (1) Pulse output_ 30 V DC, 40 mA or less... Show Detail
If the project that you want to upload includes expansion FBs provided by Fuji Electric, the expansion FBs must be installed on your computer. Install the ex... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail
It may be caused by noise. Check the surrounding environment and wiring routes for any problem. The lowered communication speed is assumed to be because t... Show Detail
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A). Show Detail
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB. After writing, the power (or reset) o... Show Detail
Can I upload a definition file downloaded from a configurator to NP1L-PD1/PD2?
No, you cannot upload a definition file. So, it is very important to keep backup of Definition file on PC side. Show Detail