One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
Is broadcast communication via Ethernet possible?
It is possible as long as the protocol is UDP/IP. In the M_OPEN FB, specify 255.255.255.255 as the IP address to be set for the 'communication destination s... Show Detail
I cannot download a project to the user ROM card inserted in the CPU. What is a possible cause?
This problem is probably caused by the following reasons: [For SPH300/2000/3000 series] 1) The CPU mode selection switch is not set at the 'UROM-TERM' pos... Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
It depends on your CPU model and how often you conduct regular inspection. The backup time after a battery error is detected is as follows. NP1PS-32/32R:... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
This is because the SX bus loop-back plug is not connected. Connect a loop-back plug to the base board. Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Yes, it is the same. Show Detail