Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of... Show Detail
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
I cannot download a project to the user ROM card inserted in the CPU. What is a possible cause?
This problem is probably caused by the following reasons: [For SPH300/2000/3000 series] 1) The CPU mode selection switch is not set at the 'UROM-TERM' pos... Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail
Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
UI4 is not supported by the specification with the VB automation interface. Meanwhile, UI4 is supported by the custom interface specification. Show Detail
Input an arbitrary address. This setting is ignored for the unpassive mode. Show Detail
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail