(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks). (2) High-performance CPU_ Access takes place when a request is generated rega... Show Detail
I cannot register a dummy module (Type_ NP1F-DMY) with the system definitions using the loader.
The purpose of a dummy module is to use it as a temporary replacement of an I/O module that has been defined with the system but does not actually exist for ... Show Detail
NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't. Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
In the system definition, group-type slave stations in any I/O configuration are registered as 'DeviceNet capsule.' In addition, the numbers of input and out... Show Detail
There are two ways to connect a USB port of a personal computer and a CPU: 1) Connect to the USB port of the CPU (directly connected to the USB cable). 2) ... Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
Does the general-purpose communication module support the BSC procedure?
No, it doesn't. Show Detail