I want to access the data memory in the MICREX-SX CPU from a PC via the RS-232C port of the general-purpose communication module. (Data read/write)
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode.
Various loader commands have been...
Show Detail
-
I will use the analog voltage input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor.
Show Detail
- No:1622
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
What is the rated current value of the fuse in the power supply module (NP1S-22)? I want to know to select the circuit breaker on the primary side ...
The rated current is 3 A.
Show Detail
- No:1641
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use the Ethernet module (NP1L-ET1/ET2) and using communication FB (M_OPEN). M_OPEN sets two ports of RPORT_NO and SPORT_NO. Does this mean that o...
One M_OPEN consumes one port of SPORT_NO, which is the local port.
RPORT_NO is the port of the other end of the communication seen from the SX.
Show Detail
-
When I try to register a remote I/O master module using the I/O extension function in a multi-CPU configuration in the system definition, an error ...
No, you cannot use the I/O extension function in a multi-CPU configuration.
Register a remote I/O master module in the normal mode or extension mode in a...
Show Detail
- No:1651
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
I converted SEL/DSEL instructions of MICREX-F to SX referring to manual FEH588-2. However, warning appeard 'DL** is overlapped with address range f...
This warning appears when the memory (DL) that is assigned to file declaration created for the timer/counter current values overlaps
with the DL memory that...
Show Detail
-
When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, ho...
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro...
Show Detail
-
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_
(1) Set the data within the user application
(2) Use 'PID FB parameter support ut...
Show Detail
- No:1296
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 14:18
- Category:
Function
-
Is there any way to check the vendor ID, product code, product revision, serial No., etc. of the slave from the DeviceNet master module (Type_ NP1L...
Unfortunately, information in a device connected to the master module cannot be read even by building a user application.
Please use the dedicated configura...
Show Detail
-
Please tell me the wiring method for the positioning control module (Type_ NP1F-MP2/MA2) when the EMG signal and ±OT signal are not used.
When the EMG signal and ±OT signal are not used, connect them to 24 V DC.
Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ...
Show Detail
- No:1432
- Displayed Date:2023/04/25 19:00
- Category:
Function