The SPH300EX (Type_ NP1PS-74D) has an SX bus connector. Which ports should I use when connecting the SX bus cable to the SX bus expansion base, 'IN...
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector.
When you connect SX bus equipment, connect the cable to the IN (input)...
Show Detail
- No:1535
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Can I use a base board with station No. setup function (Type_ NP1B*-**S) as a standard base board (without 'S' at the end of type code)?
You can use it as a standard base board by setting its station No. to '00.' In this case, you also need to set the system definition of the loader designed f...
Show Detail
- No:1531
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/09 13:50
- Category:
Main unit
-
How does the redundant system handle tasks being executed when the operation is switched from an operating CPU to a standby CPU?
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task.
Show Detail
- No:1530
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Can I use both P-link and PE-link in one system?
No, you cannot.
Show Detail
-
I converted an M/F program into an SX program with the Standard loader. I performed simulation of the converted program in the Standard loader, but...
The simulation function of the StandardV3 does not support the index register.
Check the program operation using a hardware PLC.
Show Detail
-
I use the Ethernet module (Type_ NP1L-ET1/ET2) in the Loader command mode. Can I also use the UDP/IP communication?
The Loader command mode is fixed to the TCP/IP communication.
UDP/IP communication is not supported.
Show Detail
-
Please tell me the wiring method for the positioning control module (Type_ NP1F-MP2/MA2) when the EMG signal and ±OT signal are not used.
When the EMG signal and ±OT signal are not used, connect them to 24 V DC.
Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ...
Show Detail
- No:1432
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Is there any way to check the vendor ID, product code, product revision, serial No., etc. of the slave from the DeviceNet master module (Type_ NP1L...
Unfortunately, information in a device connected to the master module cannot be read even by building a user application.
Please use the dedicated configura...
Show Detail
-
With the general-purpose communication module (Type_ NP1L-RS□), in what cases does 'C0_ Hardware error detected during receiving' occur?
It occurs when any of the overrun, parity and framing errors is detected in the serial port of a general-purpose communication module.
Show Detail
-
With the pulse train output positioning control module (Type_ NP1F-HP2), positioning has ended but the end signal is not generated.
If the start bit remains on, the positioning end signal is not generated.
Show Detail
- No:1317
- Displayed Date:2023/04/25 19:00
- Category:
Function