In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p...
Show Detail
- No:1390
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I understand that an analog input module (Type_ NP1AXH4-MR, etc.) has a signal line breakage detection function. How does it work?
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided.
An input voltage of 0.92 V or lower for the 1 to 5 V ran...
Show Detail
- No:1316
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
With the high-speed output module (Type_ NP1Y32T09P1-A), the LED flashes but no pulse is output to the outside. What should I check?
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated.
If no pulse output is generated in t...
Show Detail
- No:1291
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
In a redundant system (SPH300 or SPH2000 with StandardV3), when I change the program online (Load the changed program into PLC), is the changed pr...
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing
by, the changed program is loaded into both CPUs...
Show Detail
-
Can I use a commercially available LAN cable as a loader cable that is used with the converter (Type_NP4H-CVU) to connect a personal computer loade...
No, you cannot.
Use the dedicated loader cable (Type_NW0H-CA3).
Show Detail
- No:1511
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
I want to connect wiring for ±OT input with the four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) but the unit does not have the te...
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal.
You can solve this problem by using software a...
Show Detail
- No:1447
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When I adjust the gain/offset of an already scaled channel on the analog input module, do I need to repeat scaling?
Since the conversion accuracy after a scaling change remains within the specifications, rescaling is unnecessary.
Show Detail
- No:1430
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
If I order one SX bus loop-back plug (Type_ NP8B-BP), how many plugs will be delivered? Does it mean a set of two plugs?
An order for one NP8B-BP means one plug will be delivered.
If you need two plugs, order two pieces. The CPU module (Type_ NP1P***) and integrated type int...
Show Detail
- No:1338
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Accessory
-
With D300win, I used a non-procedural FB (_C_free) in a program for compilation and an error occurred. What is the cause of this problem?
One possible cause is that common FB _C_COM is not registered with the library.
For communication-related expansion FBs including _C_FREE, register common...
Show Detail
-
I use the pulse train output positioning control module (Type_ NP1F-HP2). Please tell me the rated voltage/current of the pulse output and control ...
Both the pulse output and control output are open collector outputs. They should be used within the following ranges
(1) Pulse output_ 30 V DC, 40 mA or less...
Show Detail
- No:1602
- Displayed Date:2023/04/25 19:00
- Category:
Function