Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
When you use battery-less operation on the SPH, is the history of RAS information recorded?
During battery-less operation, previous fault information and other 'history of RAS' are not saved. Only the present RAS information is displayed. Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail
No, you cannot use the I/O extension function in a multi-CPU configuration. Register a remote I/O master module in the normal mode or extension mode in a... Show Detail
Modules that use the processor bus, such as the P/PE link and FL-net modules, need be mounted on the slot equipped with the processor bus. Other communicati... Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail