I want MICREX-SX SPH models designed to resist sulfurized gas.
You can order sulfurized gas-resistant models by adding /Z4 at the end of product type code of the MICREX-SX SPH. Or, contact your Fuji Electric sales repres...
Show Detail
- No:1425
- Displayed Date:2023/04/25 19:00
- Category:
Others
-
When the retain memory (memory for data backup with a battery) of the CPU module of the MICREX-SX Series SPH is corrupted, how does the CPU module ...
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this...
Show Detail
- No:1611
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use an Ethernet module (Type_ NP1L-ET□) in a redundant system. Is processing such as reopening of the Ethernet required at the time of redundancy...
The SPH system automatically inherits information such as the communication ports and reopening processing is not required.
Show Detail
-
Is the measurement accuracy affected when an external arrestor for protection is mounted on the input terminal of the thermocouple input module (Ty...
The influence of external resistance on the thermocouple input is approximately 0.3 ?V/?.
The measurement accuracy of the thermocouple input is affected by...
Show Detail
- No:1545
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
I will use the analog current input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
No, you can't.
The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ...
Show Detail
- No:1603
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
With an Ethernet module (Type_ NP1L-ET1/ET2), is the protocol for fixed buffer communication the same as that of MICREX-F?
Yes, it is the same.
Show Detail
-
Does the PROFIBUS-DP master/slave module (Type_ NP1L-PD1/PS1) support the DPV1 (message communication) function?
No, it does not support the DPV1 function.
It supports the DPV0 (I/O communication) function.
Show Detail
-
Please tell me the wiring method for the positioning control module (Type_ NP1F-MP2/MA2) when the EMG signal and ±OT signal are not used.
When the EMG signal and ±OT signal are not used, connect them to 24 V DC.
Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ...
Show Detail
- No:1432
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
An address error occurs when I read a battery error of the standby CPU (CPU1) from the operating CPU (CPU0).
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr...
Show Detail
- No:1572
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
Does the accuracy specification of the thermocouple input module (Type_ NP1AXH4-TC) include zero junction compensation accuracy?
The measurement accuracy does not include zero junction compensation accuracy.
The zero junction compensation accuracy is ±1°C (at ambient temperature 0°C ...
Show Detail
- No:1597
- Displayed Date:2023/04/25 19:00
- Category:
I/O