With a general-purpose communication module, is RS232C completely full duplex?
It is full duplex for both hardware and software (firmware) for anything other than communication by M_RECEIVE and M_SEND on the SX bus, which are FB interna... Show Detail
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later. [Related document] Refer to Section '11-7 Sampl... Show Detail
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
No, they do not have polarity because they use relay contacts. Show Detail
No, the Ethernet module does not support the AUTO-MDI/MDIX function (Auto-switching of straight/cross cable.) The applicable cable type depends on whether ... Show Detail
No, you cannot. Use the dedicated loader cable (Type_NW0H-CA3). Show Detail
What is the transfer data size range for the READ_WORD/WRITE_WORD FB?
The range in terms of description is up to 4096 words respectively. Note, however, that actual message transfer on the SX bus takes place after division into... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail
131-140 of Total 235