How can I change the CPU type in an already created project?
Refer to 'Appendix 3-2 Procedure for Changing Resource (CPU type)' in the User's Manual 'Instructions' (FEH200 with index 'o' or later). Show Detail
Please tell me how to register a T-link model of UG (or V Series) as a POD in the system definition.
Select a T-link capsule and set the numbers of input/output words. By default, a POD requires one word for input and one word for output. Show Detail
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la... Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
No, it does not support the DPV1 function. It supports the DPV0 (I/O communication) function. Show Detail
The SX bus station number for the slot on which the CPU module is mounted is recognized as unused. Show Detail
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.) The rated current is 40 mA and an encoder that permits t... Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Does the general-purpose communication module support the BSC procedure?
No, it doesn't. Show Detail