It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr... Show Detail
Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
The temperature measurement value of the resistance temperature sensor (PT input) is unstable.
If this is caused by a fluctuation in the input temperature, moving average processing shown below may improve the condition. 1) Change the digital filter v... Show Detail
Is the SX bus cable oil resistant?
The cable is not oil resistant so that you need to protect it by covering it with oil-resistant material. Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail