Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
A 'client' is a device that collects data. Since the PLC is a device from which data is collected, there is no OPC client. Show Detail
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't. Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica... Show Detail
I want to equalize filter instructions in a redundant system.
Filter instructions are system FBs. System FBs that can be equalized are limited to_ The last value of the edge detection FB, present counter value of the co... Show Detail
No, you can't. The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ... Show Detail
Is the backup battery consumed while the control power supply of the CPU is active?
The backup battery is intended to back up the data memory (SRAM) inside of the CPU. While the system is turned on, the power is supplied from the control pow... Show Detail
The data written with the F_WRITE FB is in a binary format. Consequently, it can be manipulated with commercial binary editors. Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail