The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks). (2) High-performance CPU_ Access takes place when a request is generated rega... Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1]. The interrupt input sig... Show Detail
There is a high-capacity battery for SPH300 (Type_ NP8P-BTS). Its battery capacity (approximately 2700 mA) is about 2.7 times that of the backup battery supp... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail