Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr... Show Detail
How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
There is a high-capacity battery for SPH300 (Type_ NP8P-BTS). Its battery capacity (approximately 2700 mA) is about 2.7 times that of the backup battery supp... Show Detail
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1]. The interrupt input sig... Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks). (2) High-performance CPU_ Access takes place when a request is generated rega... Show Detail