What is necessary for MODBUS_RTU communication between SPH and an external device?
The following are necessary. 1) Hardware: General-purpose communication module (NP1L-RS1/RS2/RS3/RS4/RS5) whose firmware version is V42 or later ... Show Detail
The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5). Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
The existing MICREX-F program does not need any modification. Show Detail
The SPH system automatically inherits information such as the communication ports and reopening processing is not required. Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
The high-speed output module (Type_ NP1Y32T09P1-A)/high-speed input module (Type_ NP1X3206-A) cannot be mounted on the T-link expansion (RT1). Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards. NP1L-FL1 : FL-netVer1 NP1L-FL2 : FL-netVer2 NP1L-FL3 : FL-netVer3(Class1) In FL-... Show Detail