I want to equalize filter instructions in a redundant system.
Filter instructions are system FBs. System FBs that can be equalized are limited to_ The last value of the edge detection FB, present counter value of the co... Show Detail
NP4H-CB2 cannot be combined with a BLACK BOX converter for use. Use NP4H-CB2 in combination with a converter NW0H-CNV (for RS-232C) or NP4H-CVU (for USB). Show Detail
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later. [Related document] Refer to Section '11-7 Sampl... Show Detail
In Standard loader, to access the input memory from MONITOUCH, cancel the I/O group setting of the input specified as 'no equipment.' If the input specified... Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this... Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail