The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
No, you cannot. Use the dedicated loader cable (Type_NW0H-CA3). Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
When you use battery-less operation on the SPH, is the history of RAS information recorded?
During battery-less operation, previous fault information and other 'history of RAS' are not saved. Only the present RAS information is displayed. Show Detail
No, they do not have polarity because they use relay contacts. Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail