What is the difference between the LG and FG terminals of the power supply module (Type_ NP1S-22)?
The LG terminal is a line filter ground terminal in the power supply module. It is intended for guiding any external noise produced in the power supply or sw... Show Detail
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this... Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail
You can connect an SX series CPU to D300win via USB, Ethernet or a dedicated loader cable, depending on the model. Configure the communication settings acco... Show Detail
NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
No, it does not support the DPV1 function. It supports the DPV0 (I/O communication) function. Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
Modules that use the processor bus, such as the P/PE link and FL-net modules, need be mounted on the slot equipped with the processor bus. Other communicati... Show Detail