With D300win, I used a non-procedural FB (_C_free) in a program for compilation and an error occurred. What is the cause of this problem?
One possible cause is that common FB _C_COM is not registered with the library.
For communication-related expansion FBs including _C_FREE, register common...
Show Detail
-
If I order one SX bus loop-back plug (Type_ NP8B-BP), how many plugs will be delivered? Does it mean a set of two plugs?
An order for one NP8B-BP means one plug will be delivered.
If you need two plugs, order two pieces. The CPU module (Type_ NP1P***) and integrated type int...
Show Detail
- No:1338
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Accessory
-
What is the difference in the open-collector pulse input between the high-speed counter (Type_ NP1F-HC2) and the multi-channel counter (Type_ NP1F-...
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req...
Show Detail
- No:1341
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
With D300win V2, I created global variables first and edited a ladder but some variables do not appear on the pull-down list for variable name inpu...
One likely cause is that any of the following characters is used in the variable worksheet
(1) A double-byte space is used. Use a single-byte space or tab...
Show Detail
-
I compiled a project of the SPH Series and came across a memory shortage error. Is there any way to deal with this problem?
With the SPH Series, the memory boundaries between the non-retain, retain, system FB and user FB memory areas can be changed to change the size of the respec...
Show Detail
-
Is it possible to read and write the IP address and port reference number of an Ethernet module (Type_ NP1L-ET1) by using a user application?
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB.
After writing, the power (or reset) o...
Show Detail
-
Is it possible to have redundant (duplicate) Ethernet communication via the Ethernet interface module (Type_ NP1L-ET1/ET2) in a redundant system of...
The redundant function of the SPH Series provides redundancy only for the CPU and it cannot make the Ethernet redundant.
Show Detail
-
When does the standard expansion FB for communication_ Cfrp2 refresh the port status in the structure variable_ RAS?
It takes place only when data are received from an external device.
Show Detail
-
Can I use a commercially available LAN cable as a loader cable that is used with the converter (Type_NP4H-CVU) to connect a personal computer loade...
No, you cannot.
Use the dedicated loader cable (Type_NW0H-CA3).
Show Detail
- No:1511
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
Can I install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) in the vertical direction on the panel?
Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca...
Show Detail
- No:1520
- Displayed Date:2023/04/25 19:00
- Category:
I/O