The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
The measurement accuracy does not include zero junction compensation accuracy. The zero junction compensation accuracy is ±1°C (at ambient temperature 0°C ... Show Detail
Timers (or other FBs such as counters) each have an internal memory that is called an instance. Therefore, after copying a timer, you need to define a vari... Show Detail
To input the initial value, input '[value, value, ..., value].' In brackets, input values and use commas to separate values. Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail
It is possible by preparing two types of power supply for driving the transistor device and the load. Refer to the User's Guide, which provides explanatio... Show Detail