How much space is necessary between the SPF series main unit and each expansion unit?
You can install the SPF series main unit and each expansion unit without space between them. Show Detail
Do addresses of T-link devices (slave stations) connected to T-link need to be consecutive?
No, they do not need to be consecutive. If there are a lot of unused addresses, it may be better to assign addresses at some intervals for the future expa... Show Detail
The following loader software and adapter are required. 1) Loader software ・NP4H-SWN The product CD of NP4H-SWN includes the loader software 'MICREX... Show Detail
No, you cannot. Use NW0H-CNV (RS-232C/RS-422 converter) or NP4H-CVU (USB/RS-422 converter) in combination with NW0H-CA3 Show Detail
Possible causes are as follows: 1) The baud rate differs between the PLC and the target device. 2) The stop bit differs between the PLC and the target devi... Show Detail
A nonfatal fault of the takt cycle monitoring error has occurred. What is a possible cause?
The takt cycle monitoring error is caused by the following factors_ (1) The preset takt cycle value specified in the system definition is shorter than the ac... Show Detail
No, you cannot use NW0H-CNV. The RS-232C/422 converter for personal computer loaders (Type_NW0H-CNV) needs to be supplied power from the PLC side, however, t... Show Detail
Which OS does MICREX-F PLC Programmer support?
The supported Windows OS depends on the loader version. Windows 7: V1.3.3.2 or later, Windows 8: V1.3.4.1 or later, Windows 8.1 and 10: V1.3.5.0 or... Show Detail
Selecting the DCE mode for the communication parameter_ DCE designation keeps DSR always on. Show Detail
Is there a limit on the wiring length of P-link/PE-link cables?
Yes, both P-link and PE-link cables have limits on the wiring length. [P-link] ・Electrical transmission line Total length of electrical transmission ... Show Detail