It is possible by preparing two types of power supply for driving the transistor device and the load. Refer to the User's Guide, which provides explanatio... Show Detail
Create one project file. There are separate tasks for the respective CPUs and the assignment of POUs to tasks determines the CPU to which the program is a... Show Detail
The SPH system automatically inherits information such as the communication ports and reopening processing is not required. Show Detail
No, they are not synchronized. The configuration flag cannot be used for that application. Use the broadcast area for handshaking using the application to ... Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
How can I use the pulse count function of the high-speed input module (Type_NP1X3206-A)?
We offer the sample program using the pulse count function for the high-speed input module. You can download the sample program and How-to Guide for it from... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
I cannot register a dummy module (Type_ NP1F-DMY) with the system definitions using the loader.
The purpose of a dummy module is to use it as a temporary replacement of an I/O module that has been defined with the system but does not actually exist for ... Show Detail
Is electronic cam operation possible without using the dedicated module?
No, it is not possible. Combine the electronic cam FB package (Type_ NP4N-CAMFV3) with a positioning control module (Type_ NP1F-MP2/MA2). Show Detail
Can I change a PLC program without a programming tool?
With a CPU module of the SPH Series that supports user ROM cards (CF or SD), a user ROM card can be used to download a program to the CPU module. Show Detail