What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
I cannot register a dummy module (Type_ NP1F-DMY) with the system definitions using the loader.
The purpose of a dummy module is to use it as a temporary replacement of an I/O module that has been defined with the system but does not actually exist for ... Show Detail
This is because the SX bus loop-back plug is not connected. Connect a loop-back plug to the base board. Show Detail
No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ... Show Detail
The existing MICREX-F program does not need any modification. Show Detail
Does the general-purpose communication module support the BSC procedure?
No, it doesn't. Show Detail
For device display in StandardV3, a maximum of 2048 rows can be displayed on one window. To display WM2048 and the following addresses, click the [Next page]... Show Detail
Yes, D300win (V3.6.14.22 or later version) has the 'SXPLC simulator' function which allows you to check circuit operations on your personal computer. * Thi... Show Detail