Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
How can I change the CPU type in an already created project?
Refer to 'Appendix 3-2 Procedure for Changing Resource (CPU type)' in the User's Manual 'Instructions' (FEH200 with index 'o' or later). Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
Yes, there are. When you install an expansion FB, sample programs are installed as compressed projects (extension *.Zwt) in a folder named 'Zipped' under t... Show Detail
How can I round the result of a division with D300win?
The quotient of a division of the INT or DINT type is rounded down. Accordingly, convert it into the REAL type, perform the division as the REAL type and con... Show Detail
It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
This is because frame data with the template file names (default names) are deleted at the time of uninstallation. (Files created with new names are not dele... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
To enable the 'output value reference input,' the output module must be actually mounted. If the output module is set as 'unimplemented' in the system config... Show Detail
271-280 of Total 398