The SPH3000 series has 'high-speed program (high-speed PG) memory' area in the program memory. When you store a POU in this area, the POU execution speed be... Show Detail
When the program for the MICREX-F is converted and opened, all user FBs in the library for the MICREX-F are automatically imported and contained in these fol... Show Detail
Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
For device display in StandardV3, a maximum of 2048 rows can be displayed on one window. To display WM2048 and the following addresses, click the [Next page]... Show Detail
The rated current is 3 A. Show Detail
On the positioning module (Type_NP1F-MP2/MA2), the 'ERR' LED turns ON. What are the possible causes?
A possible cause is that a “Deviation amount over error” occurred. For details, refer to the user's manual FEH213 (NP1F-MA2) or FEH214 (NP1F-MP2) 'Section 8 ... Show Detail
The SPH system automatically inherits information such as the communication ports and reopening processing is not required. Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail
171-180 of Total 398