Does data monitoring of the I/O area require the module to be registered in the system definition?
Unless you register the module in the system definition and set the I/O group in the CPU parameters, data monitoring is disabled because no memory is reserve... Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
No, it is not necessary for normal operation. The main purposes of mounting a CF card or an SD card on a CPU module are as follows. - You can write a progr... Show Detail
Yes, it is generally possible. However, be sure to use compensating leads also for wiring to the recorder. Some recorders may not permit connection dependi... Show Detail
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB. After writing, the power (or reset) o... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail
No, you cannot use the I/O extension function in a multi-CPU configuration. Register a remote I/O master module in the normal mode or extension mode in a... Show Detail
No, they are not synchronized. The configuration flag cannot be used for that application. Use the broadcast area for handshaking using the application to ... Show Detail
It is not provided as internal memory. You need to create the circuit shown in the attached diagram. The example shows a circuit in which M0 repeats ON and O... Show Detail
You can use it as a standard base board by setting its station No. to '00.' In this case, you also need to set the system definition of the loader designed f... Show Detail