The minimum required products are (1) High-performance CPU exclusively for the electronic cam, (2) pulse train combined module (Type_ NP1F-MP2) or anal... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail
No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ... Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail
To use conversion instructions from MICREX-F (instructions with the suffix '_MF') with SH2000 or SPH3000 series, the following software version of the CPU is... Show Detail
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later. [Related document] Refer to Section '11-7 Sampl... Show Detail
A description in the brackets of an array must only include values or variable names. Writing an expression in brackets is not possible. Show Detail
Can I change a PLC program without a programming tool?
With a CPU module of the SPH Series that supports user ROM cards (CF or SD), a user ROM card can be used to download a program to the CPU module. Show Detail
What is the range of IP addresses that can be used for FL-net?
With FL-net, Class C IP addresses are used. The range of Class C IP addresses is 192.0.0.* to 233.255.255.*. (Range of *_ 1 to 254) Show Detail
To input the initial value, input '[value, value, ..., value].' In brackets, input values and use commas to separate values. Show Detail