When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
The version of the D300win is displayed as Version 4.0. Why?
This was probably caused by the following factors (1) The PC was not restarted after the D300win was installed. (2) A space is included in the name of the... Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
It counts the number of transmissions of message processing M_RECEIVE and M_SEND performed on the SX bus. Show Detail
No, they won't. The programs will be executed from top to bottom for each task to which they are assigned, 'DEFAULT,' 'FIXED_CYCLE' and 'EVENT' respectively. Show Detail
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
If battery-less operation is enabled under the 'CPU running definition' setting, the content of the retain memory is not retained. Disable battery-less opera... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail