The program memory, data memory and system definitions in the CPU can be saved to a PC as a data file by using the 'Backup' function included in the 'SX cont... Show Detail
Note the following points (1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected. (2) The Z-phase/timing input signal f... Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
The redundant function of the SPH Series provides redundancy only for the CPU and it cannot make the Ethernet redundant. Show Detail
Can a master control instruction be used in the MICREX-SX Series?
(1) For Expert (D300win) No master control instruction is provided. This is because the MICREX-SX Series is dedicated to programmable logic controlle... Show Detail
Is there an RAS that detects an error of the external power supply used for an I/O module?
No, there isn't. Receive the external power supply as an external input to detect the status. Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
With D300win V2, I cannot monitor some of the variables in the global variable worksheet.
They cannot be monitored if the number of rows in the variable worksheet exceeds 2520. Divide the variable worksheet so that the number of rows is 2500 or... Show Detail
The SX bus station number for the slot on which the CPU module is mounted is recognized as unused. Show Detail
The current value of the timer can be changed. Note, however, that a circuit for changing the current value of the timer must be added. Show Detail