When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, how is the received data treated?

Fuji Electric Global

Global
  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Communication (Others) > When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, ho...
  • No : 1672
  • Displayed Date : 2023/04/25 19:00
  • Print

When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, how is the received data treated?

When using a communication module (NP1L-RS1/RS2/RS3/RS4/RS), the FB outputs R_STS 'C0' (Hardware error detected) during receiving. In this case, how is the received data treated?
Category : 

Answer

The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal from OFF to ON) also clears the received data from the buffer.