I attempted to register 10 units of thermocouple input module (Type_ NP1AXH4-TC) on the T-link expansion (Type_ NP1L-RT1) base but it was not possible.

Fuji Electric Global

Global
  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Communication (T-link) > I attempted to register 10 units of thermocouple input module (Type_ NP1AXH4-TC) on the T-link expansion (Type_ NP1L-RT1) base but it was not possi...
  • No : 1333
  • Displayed Date : 2023/04/25 19:00
  • Print

I attempted to register 10 units of thermocouple input module (Type_ NP1AXH4-TC) on the T-link expansion (Type_ NP1L-RT1) base but it was not possible.

I attempted to register 10 units of thermocouple input module (Type_ NP1AXH4-TC) on the T-link expansion (Type_ NP1L-RT1) base but it was not possible.
Category : 

Answer

There is a limit to the number of words for the I/O modules that can be mounted on a T-link expansion (Type_ NP1L-RT1) base_ 128.
With the thermocouple input module (Type_ NP1AXH4-TC), one unit occupies 16 words and only up to eight units can be mounted on a T-link expansion module.