Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor. Show Detail
Since the conversion accuracy after a scaling change remains within the specifications, rescaling is unnecessary. Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
The temperature measurement value of the resistance temperature sensor (PT input) is unstable.
If this is caused by a fluctuation in the input temperature, moving average processing shown below may improve the condition. 1) Change the digital filter v... Show Detail