I will use the analog current input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
No, you can't.
The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ...
Show Detail
- No:1603
- Displayed Date:2023/04/25 19:00
-
I will use the analog voltage input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor.
Show Detail
- No:1622
- Displayed Date:2023/04/25 19:00
-
There are two types of AC input modules, for 100V (NP1X1610, NP1X1610-RI) and 200V (NP1X1611, NP1X1611-RI). What is the difference between the prod...
The product type without 'RI' judges ON/OFF of the inputs by current.
On the other hand, the product type with 'RI' judges ON/OFF of the inputs by voltage.
...
Show Detail
- No:1650
- Displayed Date:2023/04/25 19:00
-
When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (...
After changing the range with the rotary switch, turn off the power once and then turn it on again, and the software offset setting will be disabled.
Show Detail
- No:1667