It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail
The multiplication of the high-speed counter module is automatically set as follows depending on the input pulse form_ ・ Forward pulse + Reverse pulse_ x1 ... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1]. The interrupt input sig... Show Detail
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
Both the pulse output and control output are open collector outputs. They should be used within the following ranges (1) Pulse output_ 30 V DC, 40 mA or less... Show Detail
The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail