If the start bit remains on, the positioning end signal is not generated. Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
The MICREX-SX series positioning module 'Type_NP1F-HD2A' replaces NC1F-VP1/FGU130B. Be aware of the following points: 1) NP1F-HD2A is differential output t... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
Note the following points (1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected. (2) The Z-phase/timing input signal f... Show Detail
The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
Both the pulse output and control output are open collector outputs. They should be used within the following ranges (1) Pulse output_ 30 V DC, 40 mA or less... Show Detail