How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
The MICREX-SX series positioning module 'Type_NP1F-HD2A' replaces NC1F-VP1/FGU130B. Be aware of the following points: 1) NP1F-HD2A is differential output t... Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1]. The interrupt input sig... Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
The counter is initially set to gate mode. Counting is disabled unless you provide a 'gate signal' externally by hardware or set 'gate disabled' by software.... Show Detail
In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail
The minimum required products are (1) High-performance CPU exclusively for the electronic cam, (2) pulse train combined module (Type_ NP1F-MP2) or anal... Show Detail