In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
Pulse input type_ A-phase for the pulse and B-phase for the sign. Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
31-40 of Total 50