No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ... Show Detail
The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A). Show Detail
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail
I cannot register a dummy module (Type_ NP1F-DMY) with the system definitions using the loader.
The purpose of a dummy module is to use it as a temporary replacement of an I/O module that has been defined with the system but does not actually exist for ... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail