How can I use the pulse count function of the high-speed input module (Type_NP1X3206-A)?
We offer the sample program using the pulse count function for the high-speed input module. You can download the sample program and How-to Guide for it from... Show Detail
Usually, set the CPU No. to 0. The CPU No. 0 works as a master of an SX bus system. In a multi-CPU system or a CPU redundant system which uses multiple CPU ... Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
If the CPU modules are mounted on a hot plug base board with station No. setup function, you can replace them without turning off the power. Show Detail
Can I store multiple programs in the user ROM card (CF or SD) ?
No, it is not possible. Only one program can be stored. Show Detail
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of... Show Detail
1-10 of Total 34