Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail
No, it doesn't. A power supply module may occupy two slots (Type_ NP1S-22, NP1S-42) or one slot (Type_ NP1S-81, NP1S-91). The connector at the far left... Show Detail
Can I store multiple programs in the user ROM card (CF or SD) ?
No, it is not possible. Only one program can be stored. Show Detail
Is there an RAS that detects an error of the external power supply used for an I/O module?
No, there isn't. Receive the external power supply as an external input to detect the status. Show Detail
This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
You can mount or remove a CPU module during system operation, but not a power supply module. [Related document] For the details of hot plugging function, r... Show Detail
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
If the CPU modules are mounted on a hot plug base board with station No. setup function, you can replace them without turning off the power. Show Detail