This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
Is there an RAS that detects an error of the external power supply used for an I/O module?
No, there isn't. Receive the external power supply as an external input to detect the status. Show Detail
How can I write to the user ROM card of a standard CPU?
Turn off the write-protect switch of the user ROM card, mount it on the CPU module and transfer a program to write it to the user ROM card. Show Detail
If the CPU modules are mounted on a hot plug base board with station No. setup function, you can replace them without turning off the power. Show Detail
Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail
Usually, set the CPU No. to 0. The CPU No. 0 works as a master of an SX bus system. In a multi-CPU system or a CPU redundant system which uses multiple CPU ... Show Detail
When you use battery-less operation on the SPH, is the history of RAS information recorded?
During battery-less operation, previous fault information and other 'history of RAS' are not saved. Only the present RAS information is displayed. Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
1-10 of Total 34