NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail
No, it does not support the DPV1 function. It supports the DPV0 (I/O communication) function. Show Detail
The base board that plays the role of a hub of optical converter modules is not represented in the system definitions. When the power supply (PS) of the sam... Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards. NP1L-FL1 : FL-netVer1 NP1L-FL2 : FL-netVer2 NP1L-FL3 : FL-netVer3(Class1) In FL-... Show Detail
What is the difference between RS-485 and RS-422 ?
RS-485 is upper compatible with RS-422. In general, RS-422 devices mainly use 4-wire connection method, while RS-485 devices mainly use 2-wire connection met... Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
1-10 of Total 53