What is the difference between RS-485 and RS-422 ?
RS-485 is upper compatible with RS-422. In general, RS-422 devices mainly use 4-wire connection method, while RS-485 devices mainly use 2-wire connection met... Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Yes, it is possible. Of the parameter setting items of initialization, changes made to specific parameter items (such as frame detection, code conversion and... Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro... Show Detail
Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
In MICREX-SX, a scan list is automatically created by registering the remote I/O to be connected to the master module in the system configuration definitions... Show Detail
The number of M_OPEN FBs that can be opened simultaneously is limited to 56. The number of FBs that can be simultaneously opened for each module depends on t... Show Detail
Common memory 1 and common memory 2 are handled together in terms of timing. However, to maintain the uniqueness of data including those in common memory 1 a... Show Detail