It counts the number of transmissions of message processing M_RECEIVE and M_SEND performed on the SX bus. Show Detail
Can I use a router for FL-net?
You cannot use a router because FL-net does not support the use of subnet. *Related document: For the notes on using FL-net, refer to 'Appendix 2-8 Differen... Show Detail
The area is cleared when the power supply is turned off once and turned on again. The P/PE link memory is located in the built-in memory (RAM) of the P/PE-l... Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
The number of M_OPEN FBs that can be opened simultaneously is limited to 56. The number of FBs that can be simultaneously opened for each module depends on t... Show Detail
What is the range of IP addresses that can be used for FL-net?
With FL-net, Class C IP addresses are used. The range of Class C IP addresses is 192.0.0.* to 233.255.255.*. (Range of *_ 1 to 254) Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail
Is it possible to use the optical converter NP1L-OL1 between processors as with the P-link?
The optical converter NP1L-OL1 is an optical converter of the SX bus. It cannot be used because the SX bus is not a link between processors. Show Detail
1-10 of Total 53