Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
It takes place only when data are received from an external device. Show Detail
What is the range of IP addresses that can be used for FL-net?
With FL-net, Class C IP addresses are used. The range of Class C IP addresses is 192.0.0.* to 233.255.255.*. (Range of *_ 1 to 254) Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
Is the SX bus cable oil resistant?
The cable is not oil resistant so that you need to protect it by covering it with oil-resistant material. Show Detail
While 'DTR_ terminal ready' can be used with RS-232C, this control line is not present for RS-485. If no response is received while data are exchanged, re... Show Detail
Are there any FL-net boards compatible with Windows 10?
※NP3L-FL3PXSの英文マニュアルなし。FAQの翻訳は実施したので、有効フラグOFFにして登録のみ実施。英文マニュアルを作った場合、公開する。(2021/1/22:光井、小笠原) NP3L-FL3PXS (PCI-Express-bus-based FL-net board) is compatible ... Show Detail
What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
What is necessary for MODBUS_RTU communication between SPH and an external device?
The following are necessary. 1) Hardware: General-purpose communication module (NP1L-RS1/RS2/RS3/RS4/RS5) whose firmware version is V42 or later ... Show Detail