The base board that plays the role of a hub of optical converter modules is not represented in the system definitions. When the power supply (PS) of the sam... Show Detail
Set the port No. as described below. (1) For NP1L-RS2_ Set '0.' (2) For NP1L-RS4_ Set '1.' See the figure below for the setting for each type of genera... Show Detail
It enables reception only when CD (Carrier Detection) is ON. (Other operations are the same as those in the DTE mode.) Show Detail
Selecting the DCE mode for the communication parameter_ DCE designation keeps DSR always on. Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory. Without handshaking, it is not... Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail