With the common memory of FL-net, I set word data with common memory 2 and bit data with common memory 1. Please describe the timing of transmissio...
Common memory 1 and common memory 2 are handled together in terms of timing. However, to maintain the uniqueness of data including those in common memory 1 a...
Show Detail
- No:1311
- Displayed Date:2023/04/25 19:00
-
With D300win, I used a non-procedural FB (_C_free) in a program for compilation and an error occurred. What is the cause of this problem?
One possible cause is that common FB _C_COM is not registered with the library.
For communication-related expansion FBs including _C_FREE, register common...
Show Detail
- No:1329
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:32
-
What is the communication protocol for the loader port of the CPU module of the MICREX-SX SPH Series?
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5).
Show Detail
- No:1379
- Displayed Date:2023/04/25 19:00
-
When I write parameter to LonWorks module (NP1L-LW1) using support tool for a LonWorks (NP4N-LNDF), what is the required cable?
You don't need a dedicated cable.
Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software.
Show Detail
- No:1676
- Displayed Date:2023/04/25 19:00
-
Which FL-net unit is responsible for refreshing data of the common memory with FL-net modules (Type_ NP1L-FL1/FL2/FL3)? Where is the master station?
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la...
Show Detail
- No:1424
- Displayed Date:2023/04/25 19:00
-
Is there any limitation on the number of M_OPENs to be executed simultaneously? If there is a limitation, what is the maximum number?
The number of M_OPEN FBs that can be opened simultaneously is limited to 56. The number of FBs that can be simultaneously opened for each module depends on t...
Show Detail
- No:1435
- Displayed Date:2023/04/25 19:00
-
Is a CPU necessary to check I/O? Input signals to the input terminals of an input module are turned ON, however, the input status LED remains OFF.
Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module.
Show Detail
- No:1537
- Displayed Date:2023/04/25 19:00
-
When the communication cable is disconnected with an FL-net module (Type_ NP1L-FL1/FL2/FL3), are the FL-net common memory data retained? Or are the...
They are retained.
Note, however, that they are cleared if the power of the FL-net module is turned off.
Show Detail
- No:1405
- Displayed Date:2023/04/25 19:00
-
Can I use both P-link and PE-link in one system?
No, you cannot.
Show Detail
- No:1523
- Displayed Date:2023/04/25 19:00
-
In an SPH system, I specified the P-link module as 'unimplemented' and the program execution time was extended. Why?
When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi...
Show Detail
- No:1355
- Displayed Date:2023/04/25 19:00