Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module. Show Detail
When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi... Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode. Various loader commands have been... Show Detail
Does an RS-485 communication module (Type_ NP1L-RS1/RS4/RS5, etc.) support the MODBUS procedure?
The SX-Programmer Expert supports MODBUS communication (master function) using an FB. Communication with a MODBUS slave device is possible by using SPH_CP... Show Detail
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5). Show Detail
It occurs when any of the overrun, parity and framing errors is detected in the serial port of a general-purpose communication module. Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail