The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro... Show Detail
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode. Various loader commands have been... Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
A 'client' is a device that collects data. Since the PLC is a device from which data is collected, there is no OPC client. Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
The existing MICREX-F program does not need any modification. Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail