Is there anything I should take note of when using an optical converter module (Type_ NP1L-OL1/OL2) as a hub on one base board?
The base board that plays the role of a hub of optical converter modules is not represented in the system definitions.
When the power supply (PS) of the sam...
Show Detail
- No:1351
- Displayed Date:2023/04/25 19:00
-
What will the operation be when the general-purpose communication parameter 8 of the non-procedure standard expansion FB for communication _Cfr* is...
It enables reception only when CD (Carrier Detection) is ON. (Other operations are the same as those in the DTE mode.)
Show Detail
- No:1598
- Displayed Date:2023/04/25 19:00
-
Is it possible to establish direct communication between Fuji Electric's PLCs and the original networks of Mitsubishi sequencers (MELSEC), NET/B, N...
The MICREX-SX does not include a communication module having interfaces with Mitsubishi's original networks, MELSEC-NET/B or NET/10 or CC-LINK.
Alternativel...
Show Detail
- No:1546
- Displayed Date:2023/04/25 19:00
-
When does the port status_ DSR (data set ready) in a structure variable_ RAS of the non-procedural standard expansion FB for communication remain on?
Selecting the DCE mode for the communication parameter_ DCE designation keeps DSR always on.
Show Detail
- No:1297
- Displayed Date:2023/04/25 19:00
-
In the communication module (NP1L-RS1/RS2/RS3/RS4/RS5), is it possible to change communication parameter such as fixed length to variable length af...
Yes, it is possible. Of the parameter setting items of initialization, changes made to specific parameter items (such as frame detection, code conversion and...
Show Detail
- No:1639
- Displayed Date:2023/04/25 19:00
-
Can I use a router for FL-net?
You cannot use a router because FL-net does not support the use of subnet. *Related document: For the notes on using FL-net, refer to 'Appendix 2-8 Differen...
Show Detail
- No:1589
- Displayed Date:2023/04/25 19:00
-
Which FL-net unit is responsible for refreshing data of the common memory with FL-net modules (Type_ NP1L-FL1/FL2/FL3)? Where is the master station?
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la...
Show Detail
- No:1424
- Displayed Date:2023/04/25 19:00
-
With communication using RS-485 of a general-purpose communication module (Type_ NP1L-RS□), is there any means to detect a line disconnection?
While 'DTR_ terminal ready' can be used with RS-232C, this control line is not present for RS-485.
If no response is received while data are exchanged, re...
Show Detail
- No:1322
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:20
-
When the power of P/PE-link is cycled, 0 data is transmitted, which I want to mask with an application. Are the configuration flag and the broadcas...
No, they are not synchronized. The configuration flag cannot be used for that application.
Use the broadcast area for handshaking using the application to ...
Show Detail
- No:1631
- Displayed Date:2023/04/25 19:00
-
In the P/PE link area, is the send area of the local station cleared when the power supply is turned off once and turned on again? Is there any set...
The area is cleared when the power supply is turned off once and turned on again.
The P/PE link memory is located in the built-in memory (RAM) of the P/PE-l...
Show Detail
- No:1436
- Displayed Date:2023/04/25 19:00