Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
Are there any FL-net boards compatible with Windows 10?
※NP3L-FL3PXSの英文マニュアルなし。FAQの翻訳は実施したので、有効フラグOFFにして登録のみ実施。英文マニュアルを作った場合、公開する。(2021/1/22:光井、小笠原) NP3L-FL3PXS (PCI-Express-bus-based FL-net board) is compatible ... Show Detail
Does an RS-485 communication module (Type_ NP1L-RS1/RS4/RS5, etc.) support the MODBUS procedure?
The SX-Programmer Expert supports MODBUS communication (master function) using an FB. Communication with a MODBUS slave device is possible by using SPH_CP... Show Detail
When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi... Show Detail
Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module. Show Detail
The number of M_OPEN FBs that can be opened simultaneously is limited to 56. The number of FBs that can be simultaneously opened for each module depends on t... Show Detail
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la... Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail