The existing MICREX-F program does not need any modification. Show Detail
Is it possible to use the optical converter NP1L-OL1 between processors as with the P-link?
The optical converter NP1L-OL1 is an optical converter of the SX bus. It cannot be used because the SX bus is not a link between processors. Show Detail
What is the range of IP addresses that can be used for FL-net?
With FL-net, Class C IP addresses are used. The range of Class C IP addresses is 192.0.0.* to 233.255.255.*. (Range of *_ 1 to 254) Show Detail
No, it does not support the DPV1 function. It supports the DPV0 (I/O communication) function. Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
Is the SX bus cable oil resistant?
The cable is not oil resistant so that you need to protect it by covering it with oil-resistant material. Show Detail
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode. Various loader commands have been... Show Detail
It occurs when any of the overrun, parity and framing errors is detected in the serial port of a general-purpose communication module. Show Detail
It takes place only when data are received from an external device. Show Detail