When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi... Show Detail
Set the port No. as described below. (1) For NP1L-RS2_ Set '0.' (2) For NP1L-RS4_ Set '1.' See the figure below for the setting for each type of genera... Show Detail
It occurs when any of the overrun, parity and framing errors is detected in the serial port of a general-purpose communication module. Show Detail
Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
Common memory 1 and common memory 2 are handled together in terms of timing. However, to maintain the uniqueness of data including those in common memory 1 a... Show Detail
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory. Without handshaking, it is not... Show Detail
What is necessary for MODBUS_RTU communication between SPH and an external device?
The following are necessary. 1) Hardware: General-purpose communication module (NP1L-RS1/RS2/RS3/RS4/RS5) whose firmware version is V42 or later ... Show Detail
In MICREX-SX, a scan list is automatically created by registering the remote I/O to be connected to the master module in the system configuration definitions... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail