Note the following points (1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected. (2) The Z-phase/timing input signal f... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
With a general-purpose communication module, is RS232C completely full duplex?
It is full duplex for both hardware and software (firmware) for anything other than communication by M_RECEIVE and M_SEND on the SX bus, which are FB interna... Show Detail
Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards. NP1L-FL1 : FL-netVer1 NP1L-FL2 : FL-netVer2 NP1L-FL3 : FL-netVer3(Class1) In FL-... Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail
The simulation function of the StandardV3 does not support the index register. Check the program operation using a hardware PLC. Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail