When I turned on the positioning control module (Type_ NP1F-MP2/MA2) in the morning, the parameters were reset to the initial values. What is the f...
Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ...
Show Detail
- No:1573
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Although the LED for ±OT lights up on the positioning control module (Type_ NP1F-MP2/MA2), the positioning operation finishes. What is the causal f...
This was probably caused by one of the following two factors_
(1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_...
Show Detail
- No:1575
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Do the blue and white cables for the ALM output of the power supply module (Type_ NP1S-22) have polarity?
No, they do not have polarity because they use relay contacts.
Show Detail
- No:1585
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use the pulse train output positioning control module (Type_ NP1F-HP2). Please tell me the rated voltage/current of the pulse output and control ...
Both the pulse output and control output are open collector outputs. They should be used within the following ranges
(1) Pulse output_ 30 V DC, 40 mA or less...
Show Detail
- No:1602
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I will use the analog voltage input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor.
Show Detail
- No:1622
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
What is the difference between the PID forward and backward operations when the PID FB package is used?
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for...
Show Detail
- No:1625
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
In a multi-CPU system, I set the 'Output reference input' of the I/O group registration but the variable (contact) specified for the output referen...
To enable the 'output value reference input,' the output module must be actually mounted. If the output module is set as 'unimplemented' in the system config...
Show Detail
- No:1637
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
Can I store multiple programs in the user ROM card (CF or SD) ?
No, it is not possible.
Only one program can be stored.
Show Detail
- No:1298
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use an Ethernet module (Type_ NP1L-ET1/ET2) to read/write data from/to a PC in the loader command communication mode. At what time are data read ...
(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks).
(2) High-performance CPU_ Access takes place when a request is generated rega...
Show Detail
-
I find the TER_LED of the T-link master module (Type_ NP1L-TL1) sometimes illuminated. The communication speed is lowered when it occurs.
It may be caused by noise. Check the surrounding environment and wiring routes for any problem.
The lowered communication speed is assumed to be because t...
Show Detail