A nonfatal fault of the takt cycle monitoring error has occurred. What is a possible cause?
The takt cycle monitoring error is caused by the following factors_ (1) The preset takt cycle value specified in the system definition is shorter than the ac... Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory. Without handshaking, it is not... Show Detail
What is the range of IP addresses that can be used for FL-net?
With FL-net, Class C IP addresses are used. The range of Class C IP addresses is 192.0.0.* to 233.255.255.*. (Range of *_ 1 to 254) Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
To enable the 'output value reference input,' the output module must be actually mounted. If the output module is set as 'unimplemented' in the system config... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
In a CPU redundant system, how can I update a program while the system is running?
Refer to the following How-to Guide, which describes how to update a program while a redundant system is running. MICREX SX How-to Guide 'How to Change Prog... Show Detail
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.) The rated current is 40 mA and an encoder that permits t... Show Detail