What is the data backup battery for the SPH Series used to back up? Are there any precautions in performing a battery-less operation?
(1) With the SPH300/2000 Series, it is used to back up the data memory of the retained attributes, calendar IC memory, and RAS information.
(2) With the SPH2...
Show Detail
- No:1534
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I used the high-speed counter module (Type_NP1F-HC2) but it doesn't count. I didn't make any settings in particular.
The counter is initially set to gate mode. Counting is disabled unless you provide a 'gate signal' externally by hardware or set 'gate disabled' by software....
Show Detail
- No:1541
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Which is the signal that indicates pulse output completion on the positioning control module (Type_ NP1F-MP2)?
Pulse output completion is indicated by the 'Command pulse zero' signal.
Normally, it is '1' to indicate the status of completion. When the number of pulses...
Show Detail
- No:1548
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
In the redundant CPU system, the cycle of the default task takes 70 ms. It takes only several microseconds with a single-CPU system. Why is such a ...
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of...
Show Detail
- No:1568
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I heard that the high-speed counter module (Type_ NP1F-HC2) requires a current value less than 40 mA for frequencies up to 50 kHz.
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed.
Show Detail
- No:1571
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
How can I provide Z-phase pulses when the equipment connected with the positioning control module (Type_ NP1F-MP2/MA2) uses a stepping motor?
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used.
Show Detail
- No:1574
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When I turned on the positioning control module (Type_ NP1F-MP2/MA2), the EMG/±OT LED lights up and positioning operation is disabled. What causes ...
Check the following two points
(1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.'
(2) Check the wiring of the external equipment. (T...
Show Detail
- No:1601
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I use the pulse train output positioning control module (Type_ NP1F-HP2). Please tell me the rated voltage/current of the pulse output and control ...
Both the pulse output and control output are open collector outputs. They should be used within the following ranges
(1) Pulse output_ 30 V DC, 40 mA or less...
Show Detail
- No:1602
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
What is the difference in the open-collector pulse input between the high-speed counter (Type_ NP1F-HC2) and the multi-channel counter (Type_ NP1F-...
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req...
Show Detail
- No:1341
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO...
Show Detail
- No:1347
- Displayed Date:2023/04/25 19:00
- Category:
Main unit