This is because the SX bus loop-back plug is not connected. Connect a loop-back plug to the base board. Show Detail
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
NP1L-RS1/RS4/RS5 support RS-485. Can I use them for RS-422 devices?
Yes, you can use NP1L-RS1/RS4/RS5 for RS-422 devices. RS-485 is upper compatible with RS-422. There are two connection types for RS-422 devices: 2-wire conne... Show Detail
NP4H-CB2 cannot be combined with a BLACK BOX converter for use. Use NP4H-CB2 in combination with a converter NW0H-CNV (for RS-232C) or NP4H-CVU (for USB). Show Detail
It depends on your CPU model and how often you conduct regular inspection. The backup time after a battery error is detected is as follows. NP1PS-32/32R:... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
The data written with the F_WRITE FB is in a binary format. Consequently, it can be manipulated with commercial binary editors. Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't. Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica... Show Detail