With a counter module (NP1F-HC2), I use 2 counter FBs to control 2 channels. At system start-up, I set simultaneous preset operations for the 2 cha...
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft...
Show Detail
- No:1640
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Does the PROFIBUS-DP master/slave module (Type_ NP1L-PD1/PS1) support the DPV1 (message communication) function?
No, it does not support the DPV1 function.
It supports the DPV0 (I/O communication) function.
Show Detail
-
How can I provide Z-phase pulses when the equipment connected with the positioning control module (Type_ NP1F-MP2/MA2) uses a stepping motor?
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used.
Show Detail
- No:1574
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I attempted to register 10 units of thermocouple input module (Type_ NP1AXH4-TC) on the T-link expansion (Type_ NP1L-RT1) base but it was not possi...
There is a limit to the number of words for the I/O modules that can be mounted on a T-link expansion (Type_ NP1L-RT1) base_ 128.
With the thermocouple inpu...
Show Detail
-
When uploading a project from CPU, the error message 'Ex.FB that import is done was not found. Import the Ex.FB using the program import function' ...
If the project that you want to upload includes expansion FBs provided by Fuji Electric, the expansion FBs must be installed on your computer. Install the ex...
Show Detail
-
I want to run an external device by pulse output with the high-speed output module (Type_ NP1Y32T09P1-A). What are the points to note regarding the...
Note the following points
(1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected.
(2) The Z-phase/timing input signal f...
Show Detail
- No:1399
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When I forget the IP address of the WEB module (Type_ NP1L-WE1), can I change the IP from an external network?
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function.
Show Detail
-
With the pulse train output positioning control module (Type_ NP1F-HP2), positioning has ended but the end signal is not generated.
If the start bit remains on, the positioning end signal is not generated.
Show Detail
- No:1317
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When I use the Ethernet module (NP1L-ET1), can I use a same message port No. (SPORT_NO) to establish multiple connections (use multiple M_OPEN)?
The SX does not allow the use of a single SPORT_NO (range_ 1 to 127) for multiple connections simultaneously. When you want to connect multiple ports, use a ...
Show Detail
-
What is the difference between the PID forward and backward operations when the PID FB package is used?
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for...
Show Detail
- No:1625
- Displayed Date:2023/04/25 19:00
- Category:
Function