Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
What is the transfer data size range for the READ_WORD/WRITE_WORD FB?
The range in terms of description is up to 4096 words respectively. Note, however, that actual message transfer on the SX bus takes place after division into... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail
Is there an RAS that detects an error of the external power supply used for an I/O module?
No, there isn't. Receive the external power supply as an external input to detect the status. Show Detail
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.) The rated current is 40 mA and an encoder that permits t... Show Detail
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB. After writing, the power (or reset) o... Show Detail
The base board that plays the role of a hub of optical converter modules is not represented in the system definitions. When the power supply (PS) of the sam... Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
191-200 of Total 235