I will use the analog voltage input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor.
Show Detail
- No:1622
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
I use the pulse train output positioning control module (Type_ NP1F-HP2). Please tell me the rated voltage/current of the pulse output and control ...
Both the pulse output and control output are open collector outputs. They should be used within the following ranges
(1) Pulse output_ 30 V DC, 40 mA or less...
Show Detail
- No:1602
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Do the blue and white cables for the ALM output of the power supply module (Type_ NP1S-22) have polarity?
No, they do not have polarity because they use relay contacts.
Show Detail
- No:1585
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Although the LED for ±OT lights up on the positioning control module (Type_ NP1F-MP2/MA2), the positioning operation finishes. What is the causal f...
This was probably caused by one of the following two factors_
(1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_...
Show Detail
- No:1575
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
When I turned on the positioning control module (Type_ NP1F-MP2/MA2) in the morning, the parameters were reset to the initial values. What is the f...
Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ...
Show Detail
- No:1573
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I used the high-speed counter module (Type_NP1F-HC2) but it doesn't count. I didn't make any settings in particular.
The counter is initially set to gate mode. Counting is disabled unless you provide a 'gate signal' externally by hardware or set 'gate disabled' by software....
Show Detail
- No:1541
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I want to connect wiring for ±OT input with the four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) but the unit does not have the te...
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal.
You can solve this problem by using software a...
Show Detail
- No:1447
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards.
NP1L-FL1 : FL-netVer1
NP1L-FL2 : FL-netVer2
NP1L-FL3 : FL-netVer3(Class1)
In FL-...
Show Detail
-
I mounted the power supply module (Type_ NP1S-22) on the base board (Type_ NP1BS-06). The connector at the far left of the base board is not used. ...
No, it doesn't.
A power supply module may occupy two slots (Type_ NP1S-22, NP1S-42) or one slot (Type_ NP1S-81, NP1S-91).
The connector at the far left...
Show Detail
- No:1340
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Main unit
-
If I order one SX bus loop-back plug (Type_ NP8B-BP), how many plugs will be delivered? Does it mean a set of two plugs?
An order for one NP8B-BP means one plug will be delivered.
If you need two plugs, order two pieces. The CPU module (Type_ NP1P***) and integrated type int...
Show Detail
- No:1338
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Accessory