When I try to register a remote I/O master module using the I/O extension function in a multi-CPU configuration in the system definition, an error ...
No, you cannot use the I/O extension function in a multi-CPU configuration.
Register a remote I/O master module in the normal mode or extension mode in a...
Show Detail
- No:1651
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
Is it possible to have redundant (duplicate) Ethernet communication via the Ethernet interface module (Type_ NP1L-ET1/ET2) in a redundant system of...
The redundant function of the SPH Series provides redundancy only for the CPU and it cannot make the Ethernet redundant.
Show Detail
-
Which is the signal that indicates pulse output completion on the positioning control module (Type_ NP1F-MP2)?
Pulse output completion is indicated by the 'Command pulse zero' signal.
Normally, it is '1' to indicate the status of completion. When the number of pulses...
Show Detail
- No:1548
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
What happens when I set the key switch of the operating CPU to STOP while using the redundancy function of the SPH300? Is the operation switched t...
This only stops the operating CPU and the operation is not switched to the standby CPU.
Show Detail
- No:1588
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?
In the system definition, group-type slave stations in any I/O configuration are registered as 'DeviceNet capsule.' In addition, the numbers of input and out...
Show Detail
-
I have configured a multi-CPU system, but the system has run out of memory for the multi-CPU. Can I access the common general memory from the other...
You cannot access general memory other than the memory for the multi-CPU from the other CPU. Access using the direct read/write FB is used for the access to ...
Show Detail
- No:1645
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I'm developing software with D300win (V2.2.5.0). Is it possible to collect data for each scan of the PLC?
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later.
[Related document]
Refer to Section '11-7 Sampl...
Show Detail
-
On the high-speed output module (Type_ NP1Y32T09P1-A), the ONL/ERR lamps are illuminated. Why does this happen?
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A).
Show Detail
- No:1342
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
What measures can I take against external noise of the high-speed counter (Type_ NP1F-HC2)?
Use the recommended shielded twisted pair cable mentioned in the User's Manual. Also provide shielding.
Show Detail
- No:1365
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
The loader connector of SPH series CPU modules has been changed into RJ45 connector. Can I use an RS-232C/422 converter for personal computer loade...
No, you cannot use NW0H-CNV. The RS-232C/422 converter for personal computer loaders (Type_NW0H-CNV) needs to be supplied power from the PLC side, however, t...
Show Detail
- No:1529
- Displayed Date:2023/04/25 19:00
- Category:
Support tool