The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
No, you can't. The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ... Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
Yes, it is the same. Show Detail
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5). Show Detail
With a general-purpose communication module, is RS232C completely full duplex?
It is full duplex for both hardware and software (firmware) for anything other than communication by M_RECEIVE and M_SEND on the SX bus, which are FB interna... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail
What is necessary for MODBUS_RTU communication between SPH and an external device?
The following are necessary. 1) Hardware: General-purpose communication module (NP1L-RS1/RS2/RS3/RS4/RS5) whose firmware version is V42 or later ... Show Detail
Can I perform broadcast communication between CPU modules without using FL-net or P/PE-link module?
The general-purpose communication function of Ethernet allows simplified broadcast communication. By using a CPU with built-in Ethernet, you can build a bro... Show Detail