How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca... Show Detail
Can I perform broadcast communication between CPU modules without using FL-net or P/PE-link module?
The general-purpose communication function of Ethernet allows simplified broadcast communication. By using a CPU with built-in Ethernet, you can build a bro... Show Detail
How can I change the CPU type in an already created project?
Refer to 'Appendix 3-2 Procedure for Changing Resource (CPU type)' in the User's Manual 'Instructions' (FEH200 with index 'o' or later). Show Detail
The MICREX-SX series positioning module 'Type_NP1F-HD2A' replaces NC1F-VP1/FGU130B. Be aware of the following points: 1) NP1F-HD2A is differential output t... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail