Messages are not displayed in the alarm tracking display.
<Causes> The bit corresponding to the message is not ON. The display mode for displaying messages is not checked in the [Alarm Device] settings of th... Show Detail
<Cause> When a control device memory bit is used to display a normal overlap or call-overlap part, only the leading edge (OFF -> ON) is recognized.... Show Detail
<TELLUS-HMI> Connection with MITSUBISHI Q series via Ethernet unit cannot be established.
Check the setting below. Screen program settings For V-SFT-6: [System Setting] > [Hardware Setting] For V-SFT-5: [System Setting] > [Device Connection... Show Detail
How to make a switch work only when the switch is held down
Follow the steps below. * If you are using the V-SFT-6, see here. [V8/TS series] Display the [Switch] dialog, select [Delay] and set for [ON delay] (uni... Show Detail
The time and date is not displayed correctly.
The solutions vary depending on the screen data settings. Check the following settings. Setting location: V-SFT editor [System Setting]→[Unit Setting]→[SR... Show Detail
Use "Text comparison". If a file agrees with another one using text comparison, they are the same screen program. Text comaprison is available to check t... Show Detail
This error may be displayed on the configuration software when data is transferred. When the V series does not respond within the set time, this error occurs... Show Detail
<V-Server> Can I specify multiple startup options?
Yes. Enter a space between each startup option. Example: V-Server is installed in "C:\MONITOUCH\V-Server": Log viewer saving + automatic termination ... Show Detail
<V-Server> Is the number of the logging to register limited on V-Server?
It depends on the version of V-Server. Version Number of the logging to register Ver.2.0.0.3 or later No limitation Ver.1.0.0.0 - Ver.2.0.0.2 Up... Show Detail
<V-Server> Can I write to the same Excel file from several different loggings?
Yes. Show Detail